FIELD TESTS ON CEMENT FOR QUALITY CONTROL PURPOSE

Field test on cement

Field Tests on Cement There are some field tests which gives some basic idea about the quality of the cement without elaborate facility of laboratory in the field. These tests are as given under Date of manufacture should be seen on the bag. It is important because the strength reduces with age. Open the bag … Read more

Physical Requirement for Grade PSC (Portland Slag Cement)-(IS-455)

When a Portland Slag cement is tested for its physical requirements, then it must satisfy the following specifications given by IS 12269. The fineness value of PSC when tested by Blaine’s air permeability method shall not be less than 225 m2/kg. The expansion value (i.e. soundness) of unaerated cement when tested by Le-Chaelier method shall … Read more

Physical Requirement for Calcined Clay based PPC (Portland Pozzolana Cement)-(IS-1489-Part 2)

When a calcined clay based Portland Pozzolana cement is tested for its physical requirements, then it must satisfy the following specifications given by IS 1489-Part 2. The fineness value of fly ash based PPC when tested by Blaine’s air permeability method shall not be less than 300 m2/kg. The expansion value (i.e. soundness) of unaerated … Read more

Physical Requirement for Fly Ash based PPC (Portland Pozzolana Cement)-(IS-1489-Part 1)

When a fly ash based Portland Pozzolana cement is tested for its physical requirements, then it must satisfy the following specifications given by IS 1489-Part 1. The fineness value of fly ash based PPC when tested by Blaine’s air permeability method shall not be less than 300 m2/kg. The expansion value (i.e. soundness) of unaerated … Read more

Physical Requirement for Rapid Hardening Portland Cement)-(IS-8041)

When a RHPC (Rapid Hardening Portland cement) is tested for its physical requirements, then it must satisfy the following specifications given by IS 8041. The fineness value of RHPC when tested by Blaine’s air permeability method shall not be less than 325 m2/kg. The expansion value (i.e. soundness) of unaerated cement when tested by Le-Chaelier … Read more

Physical Requirement for 53 Grade OPC (Ordinary Portland Cement)-(IS-12269)

When a 53 grade ordinary Portland cement is tested for its physical requirements, then it must satisfy the following specifications given by IS 12269. The fineness value of 53 grade OPC when tested by Blaine’s air permeability method shall not be less than 225 m2/kg. The expansion value (i.e. soundness) of unaerated cement when tested … Read more

Physical Requirement for 43 Grade OPC (Ordinary Portland Cement)-(IS-8112)

When a 43 grade ordinary Portland cement is tested for its physical requirements, then it must satisfy the following specifications given by IS 8112. The fineness value of 43 grade OPC when tested by Blaine’s air permeability method shall not be less than 225 m2/kg. The expansion value (i.e. soundness) of unaerated cement when tested … Read more

Physical Requirement for 33 Grade OPC (Ordinary Portland Cement)-(IS-269)

When a 33 grade Ordinary Portland cement is tested for its physical requirements, then it must satisfy the following specifications given by IS 269. The fineness value of 33 grade OPC when tested by Blaine’s air permeability method shall not be less than 225 m2/kg. The expansion value (i.e. soundness) of unaerated cement when tested … Read more

10+ GUIDELINES TO FOLLOW WHILE STORING CEMENT ON WORK SITE

cement bag storing header & stretcher style

Guidelines on Storing of Cement on Site In large work or in major construction works, cement is generally stored at site. The cement must be stored in such a manner so that, it can be easily accessible for proper inspection. The building in which cement is stored should be water tight in order to prevent … Read more